Note (acc. to DIN VDE 0100/11.85, T 520, Sect. 528.11):
Cables or lines that are insulated for the maximum operating
voltage must be used, or each conductor of a multi-wire cable/
line must be insulated for the next voltage appearing in the
cable/line.
When laying conductor lines in electrical installation pipes or
ducts only the conductors of a main power circuit including the
associated auxiliary power circuit may be laid together
Several main power circuits including the associated auxiliary
power circuits can also be combined in a single cable or line
Cables and terminals approved for use the mains voltage (230 V)
must be used for the installation
The installation must be carried out in such a way that when the
supply voltage is switched off, all signal and control cables are also
switched off at the same time
All components of the main power and control power circuits must
be designed for 250 V working voltage to ground
All the luminaires must be wired with H05 cables provided U
OUT
does not exceed 430 V
eff,
and also be subjected to an insulation
test (in accordance with VDE) in conjunction with OSRAM DALI/
DIM ECGs. OSRAM QUICKTRONIC DALI/DIM ECGs do not ex-
ceed 430 V
eff
even for T5-Ø 16 mm HE and HO florescent lamps.